Power Factor Correction Calculator

This power factor correction calculator finds capacitor power and capacitance from real power and the present and desired power factor. Example: 30 kW from 0.70 to 0.95 needs about 20.7 kvar, or 3 × 138 µF in delta at 400 V.

Source: Wikipedia – Blindleistungskompensation. Updated: .

kW
Power factor of the installation from a measurement or nameplate, between 0.05 and 1.
V
Three-phase: voltage between two lines (e.g. 400 V); single-phase: e.g. 230 V.
Hz
My ToolboxYour inputs are saved in this browser only.

Result

Result
Capacitor power Qc = 20.75 kvar, capacitance: 3 × 137.6 µF in delta
Before and after
QuantityBeforeAfter
Power factor0.70.95
Phase angle φ45.57°18.19°
Real power P30 kW30 kW
Reactive power Q30.61 kvar9.861 kvar
Apparent power S42.86 kVA31.58 kVA
Current per line61.86 A45.58 A
Steps
  • Reactive power Q = P·tan φ: before 30·tan(arccos 0.7) = 30.61 kvar, after 30·tan(arccos 0.95) = 9.861 kvar.
  • Capacitor power Qc = Q₁ − Q₂ = 30.61 − 9.861 = 20.75 kvar.
  • Delta: per capacitor C = Qc / (3·ω·U²) = 20.75 kvar / (3·2π·50 Hz·(400 V)²) = 137.6 µF.
  • The current drops from 61.86 A to 45.58 A, which is 26.32 % less.
The calculation assumes sinusoidal currents. With harmonics (frequency converters, LED drivers) detuned capacitor banks may be needed. Selection and connection belong in the hands of a qualified electrician; capacitors store charge.

How it is calculated

Inductive loads such as motors and transformers need reactive power Q in addition to real power P, which burdens the grid; capacitors supply it locally and so lower the current. Correction raises the power factor, ideally to 0.95 to 1.

The calculation

Reactive power is Q = P·tan φ. To go from power factor cos φ₁ to cos φ₂ you need the capacitor power Qc = P·(tan φ₁ − tan φ₂). For 30 kW from 0.70 to 0.95, tan φ₁ = 1.020 and tan φ₂ = 0.329, so Qc ≈ 20.7 kvar. The capacitance follows: single-phase C = Qc / (ω·U²); three-phase in delta per capacitor C = Qc / (3·ω·U²); in star C = Qc / (ω·U²), with U the line-to-line voltage and ω = 2π·f. In the example that is 3 × 138 µF in delta at 400 V and 50 Hz.

Benefit

Apparent power falls from 42.9 kVA to 31.6 kVA and the current from 61.9 A to 45.6 A, about 26 percent less. That relieves cables and transformers and can avoid reactive-energy charges.

Frequently asked questions

How do you calculate the capacitor power for power factor correction?

Qc = P·(tan φ₁ − tan φ₂). For 30 kW from 0.70 to 0.95 that is about 20.7 kvar.

How large must the capacitor be?

Single-phase C = Qc / (ω·U²). In three-phase delta each of the three capacitors needs C = Qc / (3·ω·U²), in star C = Qc / (ω·U²), with U the line-to-line voltage.

Why improve the power factor?

A low power factor means more current for the same real power. That loads cables and transformers and can cause reactive-power charges from the grid operator.