Radiator size calculator

To calculate the radiator size, enter the heat demand and operating temperatures: you see the rated output the radiator must have, plus values for common flow temperatures.

Source: Wikipedia – Heizkörper: standard output according to DIN EN 442 at 75/65/20 °C, radiator exponent n. Updated: .

W
°C
°C
°C
panel radiators about 1.3; convectors 1.3–1.4
My ToolboxYour inputs are saved in this browser only.

Result

Result
For 1,500 W of heat demand at 55/45 °C the radiator needs 2,937 W rated output (75/65/20)
Output at common flow temperatures
Flow/returnExcess temperatureFactor to rated outputrated output needed
75/65 °C49.8 K11,500 W
70/55 °C42.1 K0.8021,870 W
55/45 °C29.7 K0.5112,937 W
45/35 °C19.6 K0.2975,054 W
35/28 °C11.1 K0.14310,523 W
Mean (logarithmic) excess temperature 29.72 K, output factor 0.511 against the standard conditions 75/65/20 °C (EN 442). For new builds and renovations, have the heat load calculated room by room; this tool does not replace a heat load calculation.

How it is calculated

The lower the flow temperature, the less output a radiator gives. At 55/45 °C and 20 °C room temperature it delivers only about 51 % of its rated output; for 1500 W of heat demand you then need a radiator rated around 2940 W.

How it is calculated

The rated output applies at 75 °C flow, 65 °C return and 20 °C room temperature, which is a logarithmic excess temperature of 49.83 K. At other temperatures Q = QN · (ΔT / 49.83 K)n, with ΔT = (flow − return) / ln((flow − room) / (return − room)). The exponent n is around 1.3 for most radiators.

Good to know

Frequently asked questions

How do you calculate the size of a radiator?

Divide the heat demand of the room by the output factor at your flow temperature. The result is the rated output (75/65/20) the radiator must have in the catalogue.

How much output does a radiator give at 55/45 °C?

About half the rated output at 75/65. A radiator rated 1000 W gives roughly 510 W at 55/45 °C.

What is the radiator exponent?

The exponent n describes how strongly output rises with excess temperature. For panel radiators 1.3 is the usual value.

Is this calculator enough instead of a heat load calculation?

No. It only converts output. The heat demand of the rooms has to come from a heat load calculation.